Septic Tank Design

Value

Pre 285

Per 285

Daily flow

1080 gpd

420 gpd

Area of field

5191 sf

2100 sf

Pretreatment

2250 gallon

475 gallon

Treatment Capacity

0 gpd

500 gpd

Pump Tank

1000 gallon

750 gallon

Observed life span

15 + years

3 – 8 years


Let's consider one real life example:
Residence in Austin, TX 78734
5,164 sf residence with an Aerobic/drip system
Class II soils placed over fractured rock
Area known for groundwater problems

Determination of Design Flow, Q:
Pre 285:
0 - 1500 sf 2 BR
1500 – 1900 sf 3 BR
800 sf = additional BR
1900 sf = 3 Bedrooms
(5164 – 1900) / 800 = 4.08 additional bedrooms.
Must round up to 5 additional bedrooms.
Number of Bedrooms = 3 + 5 = 8 Bedrooms
Q = (B + 1) x 120 gpd (with a 20% credit for low flow fixtures)
Qpre-285 = (8 + 1) x 120 gpd = 1080 gpd.
Per 285:
Table III, says less than 5500 sf is 6 Bedrooms.
6 Bedrooms, Qper-285 = 420 gpd.

Determination of Field Area:
Pre 285:
No specific guidance on drip, but
Generally accepted Ra < 0.1 gpd /sf
A = Q / Ra = 1080 / 0.1 = 10800 sf
Per 285:
Fractured rock, Ra = 0.2 gpd / sf
A = Q / Ra = 420 / 0.2 = 2100 sf
Note: Area provided = 2600 sf

Sizing of Tanks:
Pre 285:
Q = 1080 gpd
Pretreatment = 1000 gallon single compartment tank
Treatment = 1250 gpd
Pump tank = 1000 gallon single compartment tank, minimum
Per 285:
Q = 420 gpd
Pretreatment = 475 gallon
Treatment = 500 gpd
Pump tank = 750 gallon

Let's consider another real life example:
Residence in Austin, TX 78734
5,164 sf residence with an Aerobic/drip system
House built on fractured rock
Area known for groundwater problems

Determination of Design Flow, Q:
Pre 285:
0 - 1500 sf 2 BR
1500 – 1900 sf 3 BR
800 sf = additional BR
1900 sf = 3 Bedrooms
(5164 – 1900) / 800 = 4.08 additional bedrooms.
Must round up to 5 additional bedrooms.
Number of Bedrooms = 3 + 5 = 8 Bedrooms
Q = (B + 1) x 120 gpd (with a 20% credit for low flow fixtures)
Qpre-285 = (8 + 1) x 120 gpd = 1080 gpd.
Per 285:
Table III, says less than 5500 sf is 6 Bedrooms.
6 Bedrooms, Qper-285 = 420 gpd.

Determination of Field Area:
Pre 285:
LPD, ET sizing due to the lack of soil.
A = 31000 (1+ 8) / (70 – 16.25) = 5191sf (in two alternating fields)
Per 285:
LPD, Fractured rock, Ra = 0.2 gpd / sf
Theoretically, A = Q / Ra = 420 / 0.2 = 2100 sf
Realistically, A = 2100*5/3 = 3500 sf.

Sizing of Tanks:
Pre 285:
Q = 1080 gpd
Pretreatment
1250 + 4(250) = 2250 gallon dual compartment tank
Pump tank = 1000 gallon single compartment tank, minimum
Per 285:
Q = 420 gpd
Pretreatment = 475 gallon
Treatment = 500 gpd
Pump tank = 750 gallon



Previous Article : Septic Tank System - - Next Article : Septic Cleaner

Featured Articles
Providing Quality Service...Guaranteed In the Greater Austin Area of Travis, Hays, Williamson, Burnet, & Bastrop Counties , Hudson Bend, Volente, Westlake Hills, Buda, Kyle, San Marcos, Florence, Brushy Creek, Leander, Misc Locations, Bell County.
Call (512) 338-1804 for fast, dependable service.
Septic Tank Additives There are many companies promoting their septic tank additives, saying they can solve all of your septic woes. For over 15 years, these claims have...
Improved Efficiency - Public And Private (Rare story: A public agency and private company work together to improve efficiency for themselves AND their customers.) Background:   Since the State-wide change in...
Maintenance Here's a logical fact of life regarding septic systems: All septic systems require maintenance to keep them working correctly and to ensure their long life....
  • Septic Drain Fields Care for your drainfieldYour drainfield is an important part of your septic system. Here are a few things...
  • Septic Tank Aerator An aerator or air pump, normally installed in a chamber atop or close to the septic tank, pumps...
  • The Best Septic System What is the best OSSF on the market?The one that is getting proper service! Even the best equipment...
  • Septic System Problems As a septic system owner you are responsible for ensuring that your septic system is safe and working...
  • Septic Tank System Minimizing the quantity of water discharged to the system on a regular basis will extend the life of...